Description Bad configuration file detected
Possible Cause
During commission/maintenance:
• The configuration file in the I/O pack or module is not compatible with loaded application code
During normal operation:
• There is a hardware failure
Solution
During commissioning or maintenance:
• Rebuild the system and download the application and the configuration to the I/O pack or module.
During normal operation:
• Replace the I/O pack or module.
263
Note This alarm is obsolete.
Description Invalid configuration file
Possible Cause
During commissioning or maintenance:
• The downloaded configuration file is for a different type of I/O module.
During normal operation:
• There is a hardware failure.
Solution
During commissioning or maintenance:
• Rebuild the control system and download the application and configuration to the I/O module.
During normal operation:
• Replace the I/O pack.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 453