6.7.5 TRLYS#F Diagnostics
Diagnostic tests to components on the terminal boards are as follows:
The voltage to each relay coil is monitored and checked against the command at the frame rate. If there is no agreement
for five consecutive frames, an alarm is latched.
The voltage across each solenoid power supply is monitored and if it goes below 16 V ac/dc, an alarm is created.
If any one of the outputs goes unhealthy a composite diagnostic alarm, L3DIAG_xxxx occurs.
Each terminal board connector has its own ID device that is interrogated by the I/O pack. The connector ID is coded into
a read-only chip containing the board serial number, board type, revision number, and the JR1/JS1/JT1 connector
location. When an ID chip is read by the I/O pack and a mismatch is encountered, a hardware incompatibility fault is
created.
The diagnostic signals can be individually latched, and then reset with the RSTDIAG signal if they go healthy.