506
Description S network shared I/O module inputs unhealthy
Possible Cause
• I/O module restarting or restarted
• I/O module application/configuration missing
• Application/configuration does not match in I/O module and controller
• Failed Ethernet connection between I/O module and controller
• Ethernet cable inserted into wrong connector on I/O module
Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the S IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812).
Solution
• Rebuild and download application/parameters to all controllers and I/O modules.
• Reload firmware and parameters to the affected I/O module.
• Reload firmware and application to all controllers.
• If the problem persists, replace the affected I/O module, then replace the controller.
507
Description T network shared I/O module inputs unhealthy
Possible Cause
• I/O module restarting or restarted
• I/O module application/configuration missing
• Application/configuration does not match in I/O module and controller
• Failed Ethernet connection between I/O module and controller
• Ethernet cable inserted into wrong connector on I/O module
Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the T IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812).
Solution
• Rebuild and download application/parameters to all controllers and I/O modules.
• Reload firmware and parameters to the affected I/O module.
• Reload firmware and application to all controllers.
• If the problem persists, replace the affected I/O module, then replace the controller.