EasyManua.ls Logo

GE Mark VIeS - Output 20;200 Ma Suicide Active; Suicide on Overcurrent, Check Terminal Board Jumper; I;O Pack Internal Power Supply Status Not OK; Dither Time Is Frozen or out of Range

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
90-91
Description Output [ ] 20/200 mA suicide active
Possible Cause
Suicide is enabled on analog output.
Review any additional diagnostics for possible causes.
The TMR_SuicLimit is set too low.
Field wiring problem
Command is beyond the range of the output.
Analog output configuration does not match hardware jumpers.
Solution
Verify that the value of TMR_SuicLimit is set correctly.
Verify that the value of D/A_ErrLimit is set correctly.
Verify the field wiring connections.
Verify that the commanded output is within output range.
92-93
Description Output [ ] Suicide on overcurrent, check terminal board jumper
Possible Cause
Incorrect setting of terminal board 20/200 mA jumper
Hardware failure in I/O pack
Solution
Check the terminal board jumper (JPO).
Replace the I/O pack.
99
Description I/O pack internal power supply status not OK
Possible Cause The internal power supply that provides analog circuit control power is not operating correctly.
Solution
Check the I/O pack ground quality through mounting bolts.
Confirm that 28 V input power is within 26.6 - 29.4 V range.
Replace the I/O pack.
100
Description Dither Time is frozen or out of range - [ ]
Possible Cause The time signal used to generate a dither on the valve output signal does not appear to being changing.
This could cause a frozen valve.
Solution
Cycle power to the I/O pack.
Replace the I/O pack.
104 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Table of Contents

Related product manuals