Note This alarm is obsolete.
Description Control/Status communication Error: [ ]
Possible Cause
Cannot get diagnostic information from I/O pack or module
I/O pack or module not able to load firmware
Solution
Verify that the I/O pack or module configuration is correct.
Rebuild the application and download the firmware and application to the I/O pack or module.
Check network cables for proper connection.
Verify that the switch is functioning correctly.
259
Description Application Runtime Error - [ ] Frame overruns occurred
Possible Cause Overloaded processor sequencer malfunction (one or more frame overruns occurred)
Solution
For a controller, perform the following to increase the frame idle time:
Reduce the application or increase the EGD period.
Upgrade the controller to one with a faster processor.
Replace the controller.
For an I/O module, perform the following:
From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module.
Replace the I/O module.