329
Description Startup sequence failed - Data initialization timeout R processor
Possible Cause Controller unable to complete startup data initialization
IONet malfunction
Controllers have different application revisions
One or more controllers powered down
Controller overloaded by external command messages
Solution
Check for disconnected IONet cables or malfunctioning network switches.
Rebuild and download the application.
Verify that all controllers are powered on.
Disable all other command senders (for example, Modbus masters) until controller is online.
330
Description Startup sequence failed - Data initialization timeout S processor
Possible Cause Controller is unable to complete startup data initialization.
IONet malfunction
Controllers have different application revisions
One or more controllers are powered down
Controller is overloaded by external command messages.
Solution
Check for disconnected IONet cables or malfunctioning network switches.
Rebuild and download application.
Ensure all controllers are powered up.
Disable all other command senders (for example, Modbus masters) until controller is online.
Controllers GEH-6855_Vol_II System Guide 51