EasyManua.ls Logo

GE Mark VIeS - JPDS Contact;Fuse; JPDG Inputs

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.2.8.3 JPDS Contact/Fuse
Variable**
Description Direction Type
DryCntStat_x_y Pbus x dry contact status (connector Jx) Input BOOL
AuxFuseStat_x_y Pbus x fuse status (connector JAx) Input BOOL
** x = R, S, T and y = 1, 2
10.2.8.4 JPDG Inputs
Parameter Description
Choices
InputDiagEnable DC or AC volt diagnostics enable
Applicable only to DC_24VFdbkMag, AC_Fdbk1_Volt_#
Enable, Disable
PS28vEnable PS 28 V feedback enable;
Enable – Enables feedback
Disable – Disables feedback and diagnostics
NoDryCnt – Enables feedback, but disables dry contact
diagnostics
Applicable only to PS28vStat
Enable, Disable, NoDryCnt
DC_24v_Trig_Volt DC 24 V fault trigger voltage
Applicable only to DC_24VFdbkMag
10 to 60
Gnd_Mag_Trig_Volt Ground magnitude fault trigger voltage
Applicable only to DC_24VGnd_FdbkMag
1 to 30
ACFdbkInVoltage AC feedback input voltage
Applicable only to AC_Fdbk1_Volt_#
100 to 250 V
ACFdbkInTol AC feedback tolerance
Applicable only to AC_Fdbk1_Volt_#
0pct, 5pct, 10pct, 20pct
Variable Description Direction Type
PS28vStat Main JPDG - PS 28 V feedback from Pbus R input AnalogInput REAL
DC_24VFdbkMag JPDG - DC 24V/48 V magnitude AnalogInput REAL
DC_24VGnd_FdbkMag JPDG - ground feedback magnitude AnalogInput REAL
AC_Fdbk1_Volt_1 Main JPDG - AC 115 to 250 V feedback input voltage AnalogInput REAL
AC_Fdbk1_Volt_2 Main JPDG - AC 115 to 250 V feedback input voltage AnalogInput REAL
316 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information