10.2.8.3 JPDS Contact/Fuse
Variable**
Description Direction Type
DryCntStat_x_y Pbus x dry contact status (connector Jx) Input BOOL
AuxFuseStat_x_y Pbus x fuse status (connector JAx) Input BOOL
** x = R, S, T and y = 1, 2
10.2.8.4 JPDG Inputs
Parameter Description
Choices
InputDiagEnable DC or AC volt diagnostics enable
Applicable only to DC_24VFdbkMag, AC_Fdbk1_Volt_#
Enable, Disable
PS28vEnable PS 28 V feedback enable;
Enable – Enables feedback
Disable – Disables feedback and diagnostics
NoDryCnt – Enables feedback, but disables dry contact
diagnostics
Applicable only to PS28vStat
Enable, Disable, NoDryCnt
DC_24v_Trig_Volt DC 24 V fault trigger voltage
Applicable only to DC_24VFdbkMag
10 to 60
Gnd_Mag_Trig_Volt Ground magnitude fault trigger voltage
Applicable only to DC_24VGnd_FdbkMag
1 to 30
ACFdbkInVoltage AC feedback input voltage
Applicable only to AC_Fdbk1_Volt_#
100 to 250 V
ACFdbkInTol AC feedback tolerance
Applicable only to AC_Fdbk1_Volt_#
0pct, 5pct, 10pct, 20pct
Variable Description Direction Type
PS28vStat Main JPDG - PS 28 V feedback from Pbus R input AnalogInput REAL
DC_24VFdbkMag JPDG - DC 24V/48 V magnitude AnalogInput REAL
DC_24VGnd_FdbkMag JPDG - ground feedback magnitude AnalogInput REAL
AC_Fdbk1_Volt_1 Main JPDG - AC 115 to 250 V feedback input voltage AnalogInput REAL
AC_Fdbk1_Volt_2 Main JPDG - AC 115 to 250 V feedback input voltage AnalogInput REAL
316 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information