34, 37
Description JPDS-[ ] P28v-T volt fdbk (JT/PT connector) out of range
Possible Cause
The 28 V Power supply input is out of range. It is expected to be within ±5% of 28 V.
The 28 V T power supply has not been connected.
There could be a power supply problem.
Solution
The input is not used. Set PS28vEnable to Disable.
Verify the power supply connections (JT/PT) to the terminal board.
Verify that the power supply feedback on the JPDS/M Inputs tab in the ToolboxST application is within the expected
tolerance (±5%).
38, 41
Description JPDS-[ ] P28v-R contact input (JR connector) indicates PS problem
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the terminal board JR connector.
The power supply contact is not used.
Solution
Verify the status of the power supply contact and that the power supply is operating correctly.
Verify the connections between the power supply and the JR connector on the terminal board.
The JR Input is not used. Set PS28vEnable to Disable.
The power supply is used, but the JR contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.