4.2 YAIC Specific Alarms
The following alarms are specific to the YAIC I/O pack.
32-41
Description Analog Input [ ] unhealthy
Possible Cause
Excitation to transducer is wrong or missing.
Transducer is defective.
Analog input current/voltage input is beyond the specified range.
Terminal board jumper settings do not match the ToolboxST configuration.
Open or short-circuit on input
Solution
Check the field wiring and connections to indicated analog input channel.
Check the field device for failure.
Verify that the configuration matches terminal board jumper settings for the indicated analog input channel.
44-45
Description Output [ ] individual current feedback unhealthy
Possible Cause
Commanded output is beyond the range of the output.
Field wiring problem
Field device problem
Open loop or too much resistance in the loop
I/O pack failed
Terminal board failed
Solution
Verify that the commanded output is within the range of the output.
Confirm the correct I/O pack 28 V input power.
Check the field wiring and device.
Replace the I/O pack.