Description The I/O pack has gone to the Offline state
Possible Cause
During commissioning or maintenance:
Ethernet cable disconnected or connected to wrong port
During normal operation:
Controller is offline or restarted.
Faulty Ethernet switch/cable
Solution
During commissioning or maintenance:
Check the Ethernet cable.
During normal operation:
Verify that the controller is not offline.
Replace the Ethernet switch/cable.
16
Description System limit checking is disabled
Possible Cause System checking disabled by configuration
Solution System checking was disabled by the configuration.