271
Description Internal communication error - Exchange [ ] Export failed
Possible Cause
During commissioning or maintenance:
I/O pack or module does not have correct configuration file stored in flash file system
Internal runtime error
During normal operation:
Internal runtime error
Solution
During commissioning or maintenance:
From the ToolboxST application, confirm the correct configuration of the I/O pack or module.
Rebuild the system, and download the application and configuration to the I/O pack or module.
During normal operation:
Restart the I/O pack or module.
If problem persists, replace the I/O pack or module.
272
Note This alarm is obsolete.
Description Internal EGD communication error - Exchange [ ] Import failed.
Possible Cause Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
273
Note This alarm is obsolete.
Description Unsupported EGD message - Invalid EGD version
Possible Cause EGD protocol version incorrect, greater than current version
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.