301
Description Configuration Load Failure
Possible Cause
• I/O pack or module I/O configuration files missing
• I/O pack or module reseated on the terminal board (clears configuration from I/O pack or module)
Solution
• Rebuild and download the application to all the processors.
• Reload the firmware and application.
• If the problem persists, replace processor module.
338
Description Pack Firmware Error - Inputs are not being updated
Possible Cause
During commissioning or maintenance:
• The I/O pack or module application process is not providing system signal inputs to EGD every frame.
Solution
During commissioning or maintenance:
• Rebuild and download the firmware and the application.
• Verify that the idle time is adequate for the I/O pack or module and that the frame rate does not exceed defined limits.
• If the problem persists, replace the I/O pack or module.
339
Description Outputs are not being received
Possible Cause
• I/O pack or module not receiving outputs from the controller after previously receiving outputs
• Controller is restarting or has restarted
• Failed Ethernet connection between the I/O pack or module and controller
• Internal firmware failure
Solution
• Check for disconnected IONet cables or malfunctioning network switches.
• Verify that the controller is online and operating correctly.
• Rebuild and download the firmware and configuration to the I/O pack or module.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 463