9.1.3 Specifications
Item
PSCA Specification
Channels
6 independently configured serial Modbus Master channels
1 Ethernet Modbus Master channel (with Simplex IONet configuration)
Communication Choices
RS-232 mode
RS-422 mode
RS-485 mode, half-duplex only
Ethernet Modbus mode
RS-232 Mode
Cable distance: 15 m (50 ft)
Communication Rate: up to 115.2 kbps
RS-422 Mode
Cable distance: 305 m (1000 ft)
Communication Rate: up to 115.2 kbps
Number of drops: 8
RS-485 Mode
Cable distance: 305 m (1000 ft)
Communication Rate: up to 375 kbps
Size
8.26 cm high x 4.19 cm wide x 12.1 cm deep (3.25 in x 1.65 in x 4.78 in)
Technology
Surface-mount
Ambient Rating for Enclosure
Design
-40 to 70ºC (-40 to 158 ºF)
Note For further details, refer to the Mark VIe Modbus Master Communication Module Summary Sheet (GEI-100868).
9.1.4 Diagnostics
The I/O pack performs the following self-diagnostic tests:
A power-up self-test that includes checks of RAM, flash memory, Ethernet ports, and most of the processor board
hardware
Continuous monitoring of the internal power supplies for correct operation
A check of the electronic ID information from the terminal board, acquisition board, and processor board to confirm that
the hardware set matches, followed by a check that the application code loaded from flash memory is correct for the
hardware set
Analog inputs such as pressure and position have system limit checking based on configurable high and low levels. These
limits can be used to generate alarms, to enable/disable, and as latching/non-latching. RESET_SYS reset the out of limits
Details of the individual diagnostics are available from the ToolboxST application. The diagnostic signals can be individually
latched, and then reset with the RESET_DIA signal if they go healthy.