EasyManua.ls Logo

GE Mark VIeS - P28 V-R Aux Output Fuse (JAR Connector) Not OK; P28 V-S Aux Output Fuse (JAS Connector) Not OK; P28 V-T Aux Output Fuse (JAT Connector) Not OK

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44, 47
Description JPDS-[ ] P28v-R aux output fuse (JAR connector) not OK
Possible Cause
The auxiliary output JAR fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
The fuse is self-resetting. Refer to help documentation.
45, 48
Description JPDS-[ ] P28v-S aux output fuse (JAS connector) not OK
Possible Cause
The auxiliary output JAS fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
The fuse is self-resetting. Refer to help documentation.
46, 49
Description JPDS-[ ] P28v-T aux output fuse (JAT connector) not OK
Possible Cause
The auxiliary output JAT fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
Fuse is self resetting. Refer to help documentation.
322 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II