Description JPDC-P28v-R contact input (JR connector) indicates PS problem.
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the specified terminal board connector.
The power supply dry contact is not used.
Solution
Verify the status of the power supply contact, and that the power supply is operating correctly.
Verify the connections between the power supply and the specified connector on the JPDC.
The input is not used. Set PS28vEnable to Disable.
The power supply is used, but the dry contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.
188
Description JPDC-P28v-S contact input (JS connector) indicates PS problem.
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the specified terminal board connector.
The power supply dry contact is not used.
Solution
Verify the status of the power supply contact, and that the power supply is operating correctly.
Verify the connections between the power supply and the specified connector on the JPDC.
The input is not used. Set PS28vEnable to Disable.
The power supply is used, but the dry contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.