8.3.4.11 KPH
[ ] = defaults
†
is only valid with YVIBS1B
Name Direction Data
Type
Description VIB_Type3 Scale Scale_Off TMR_
DiffLimit
KPH_Thrshld
GAP12_KPH2 AnalogInput REAL Average Air Gap,DC
component of input#9
Sensor Type,
group 3
[Unused],
PosProx,
†
KeyPhasor
Volts/-
mil or
Volt-
s/ips
[0.2]
0 to 2
Scale
offset for
Prox
position
only, in
mils
[0]
0 to 90
Difference
Limit for Voted
TMR Inputs in
Volts or Mils
[2]
-100 to 100
Voltage
difference from
gap voltage
where
keyphasor
triggers
[2.0]
1.0 to 5.0
GAP13_KPH1 AnalogInput REAL Average Air Gap,DC
component of
input#10
Sensor Type,
group 3
[Unused],
PosProx,
KeyPhasor
KPH_Type GnBiasOvr-
ide
Snsr_Offset Gain SysLim1E-
nabl
SysLim1-
Latch
SysLim1Type SysLimit1
[Slot],
Pedestal
Gain Bias
Override
[Disable],
Enable
Amount of bias
voltage (dc) to
remove from input
signal used to
max. A/Ds signal
range used only
when
GnBiasOvride is
enabled
[10]
±13.5
Resolution of
input signal
(net gain
unchanged),
select based
on expected
range, use
only if
GnBiasOvride
is enabled
[1x],
‡
2x, 4x,
‡
8x
Enable System
Limit 1
[Disable],
Enable
Latch the
alarm
[Latch],
NotLatch
System Limit 1
Check Type
[ >= ] , <=
System
Limit 1 –
GAP in
negative
volts
(Velomitor)
or positive
mils (Prox)
[90]
-100 to 100
‡
Gain 2x and Gain 8x are Never valid on GAP12_KPH2.
SysLim2Enabl SysLim2Latch SysLim2Type SysLimit2
Enable System Limit 2
[Disable], Enable
Latch the alarm
[Latch], NotLatch
System Limit 2 Check Type
[ >= ] , <=
System Limit 2 – GAP in
negative volts (Velomitor) or
positive mils (Prox)
[10]
-100 to 100
YVIB Vibration Monitor Modules GEH-6855_Vol_II System Guide 269
Public Information