GE Mark VIeS - Configuration File Load Error - Invalid Header Size

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
368
Description Configuration file load error - invalid header size
Possible Cause
During commissioning or maintenance:
Build error
Controller EGD revision code not supported
Incompatible version of I/O pack or module firmware was downloaded
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module
During normal operation: Replace the I/O pack or module.
369
Description Internal communication error - Exchange [ ] Export failed
Possible Cause Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
370
Note This alarm is obsolete.
Description Internal EGD communication error - Exchange [ ] Import failed
Possible Cause Internal runtime error
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 469