Note This alarm is obsolete.
Description EGD communication terminated
Possible Cause Internal runtime error
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• If the problem persists, replace the I/O pack or module.
366
Description Initialization failure - IO firmware
Possible Cause I/O pack or module did not initialize correctly
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• Download the firmware and application code.
• If the problem persists, replace the I/O pack or module.
367
Description Internal communications error - HSSL Comm link down
Possible Cause Internal runtime error
Solution
• Check the High Speed Serial Link (HSSL) cables.
• Upgrade the I/O pack or module firmware and application code.
• Download the firmware and application code.
• If the problem persists, replace the I/O pack or module.