Terminal Board Fuses
Relay
Output
Circuit #
TRLYH1B/-
S1B
TRLYH#C TRLYH1D/-
S1D
TRLYH#F/S#-
F with WPDF
SRLY_2A
with
WROB
SRLY_2A
with WROF
SRLY_2A with
WROG
1 FU1
FU7
FU1
FU7
FU1
FU7
FU1
FU13
FU1
FU7
FU1 FU1
2 FU2
FU8
FU2
FU8
FU2
FU8
FU2
FU14
FU2
FU8
FU2 FU2
3 FU3
FU9
FU3
FU9
FU3
FU9
FU3
FU15
FU3
FU9
FU3 FU3
4 FU4
FU10
FU4
FU10
FU4
FU10
FU4
FU16
FU4
FU10
FU4 FU4
5 FU5
FU11
FU5
FU11
FU5
FU11
FU5
FU17
FU5
FU11
FU5 FU5
6 FU6
FU12
FU6
FU12
FU6
FU12
FU6
FU18
FU6
FU12
FU6 FU6
7
Not fused Not fused N/A FU7
FU19
Not fused FU7 FU7
8 Not fused Not fused N/A FU8
FU20
Not fused FU8 FU8
9 Not fused Not fused N/A FU9
FU21
Not fused FU9 FU9
10 Not fused Not fused N/A FU10
FU22
Not fused FU10 FU10
11 Not fused Not fused N/A FU11
FU23
Not fused FU11 FU11
12 Not fused Not fused N/A FU12
FU24
Not fused FU12 FU12
142
Description All fuses blown or no terminal board excitation
Possible Cause If fuse sensing indicates an open fuse, this may be due to loss of input power to the terminal board.
Without power to the fuses, the sensing may indicate a false open-fuse condition.
Solution
• Confirm the correct input power to the terminal board.
• Check the I/O pack connector alignment and seating.
• Check the I/O pack configuration.
• Check all fuses.
• Replace the I/O pack.
• Replace the terminal board.