280
Description Platform hardware does not match configuration
Possible Cause
• During commissioning or maintenance, the platform type identified in the application configuration does not match
actual hardware
• During normal operation, there is a hardware failure
Solution
• From the General tab, select General Properties, and Platform and fix the platform type.
• Rebuild and download the application.
• If the problem persists, replace the I/O pack or module.
281
Description Firmware Load Error - FPGA not programmed due to platform errors
Possible Cause File downloaded to configure the Field Programmable Gate Array (FPGA) not successfully applied
Solution
• Verify that all connectors are aligned properly and fully seated.
• Check the firmware version for compatibility with platform. If it is correct, replace the I/O pack or module.
282
Description Firmware Load Error - application independent processes failed to initialize
Possible Cause Runtime malfunction. An application-independent firmware process could not be started successfully.
Solution
• Reload firmware and application and restart.
• Controller: If the failure persists, remove the Compact Flash module and reprogram the boot loader using the ToolboxST
configuration. Download using the Device | Download | Controller setup | Format Flash selection. After reinstalling the
flash module and restarting, reload the firmware and application.
• Replace the module.
• I/O pack or module: Re-download the base load.
283
Description Firmware error - Internal process crashed
Possible Cause Runtime or hardware malfunction (runtime process failed)
Solution
• Reload firmware and application and restart.
• Re-download the baseload and the firmware.
460 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II