277
Note This alarm is obsolete.
Description IONET-EGD - Exchange [ ] Signature mismatch from Producer [ ], expected [ ], received [ ]
Possible Cause Message version mismatch
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• If the problem persists, replace the I/O pack or module.
278
Note This alarm is obsolete.
Description IONET-EGD - Producer [ ] gave bad length Exchange [ ], expected [ ], got [ ]
Possible Cause Exchange message wrong length
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• If the problem persists, replace the I/O pack or module.
279
Description Could not determine platform type from hardware
Possible Cause
• During commissioning or maintenance, there is an incorrect firmware version or hardware malfunction (firmware could
not recognize host hardware type)
• During normal operation, there is a hardware failure
Solution
• Verify that all connectors are aligned properly and fully seated.
• Check the firmware version for compatibility with platform. If it is correct, replace the I/O pack or module.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 459
Public Information