Note This alarm is obsolete.
Description IONET-EGD - Received Redundant Exchange from unknown address
Possible Cause Controller received EGD message from unknown address
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
275
Note This alarm is obsolete.
Description IONET-EGD - Out of order Exchange [ ] from Producer [ ], Rcvd [ ], Last [ ]
Possible Cause Message sequence number was out of order, less than required
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
276
Note This alarm is obsolete.
Description IONET-EGD - UNHEALTHY (Bad Configuration Time) Producer [ ], Exchange [ ]
Possible Cause Message version mismatch
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.