Description JPDS-[ ] P28v-S contact input (JS connector) indicates PS problem
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the terminal board JS connector.
The power supply contact is not used.
Solution
Verify the status of the power supply contact and that the power supply is operating correctly.
Verify the connections between the power supply and the JS connector on the terminal board.
The JS Input is not used. Set PS28vEnable to Disable.
The power supply is used, but the JS contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.
40, 43
Description JPDS-[ ] P28v-T contact input (JT connector) indicates PS problem
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the terminal board JT connector.
The power supply contact is not used.
Solution
Verify the status of the power supply contact and that the power supply is operating correctly.
Verify the connections between the power supply and the JT connector on the terminal board.
The JT Input is not used. Set PS28vEnable to Disable.
The power supply is used, but the JT contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.