99-130
Description IOPoint [ ] - Current output commanded current feedback error
Possible Cause
The measured current feedback does not match the commanded current.
There is an open circuit on an output.
Output impedance is too high (max allowed 800 Ohms).
Solution
Check the field wiring and device.
Verify that the commanded output is within output range.
Replace the I/O pack.
131-162
Description IOPoint [ ] - Open field wire detected
Possible Cause An open circuit has been detected at the terminal board based on the sensor type.
Solution
Digital Input:
Check the wiring between the terminal board and the device.
Verify that the recommended line monitoring resistors are being used (refer to the I/O pack user documentation).
Thermocouple Input: verify the wiring of the thermocouple at the inputs.
163-194
Description IOPoint [ ] - Thermocouple input millivolt exceeds hardware limit ([ ] mV)
Possible Cause
Thermocouple millivolt input exceeds the hardware limit
An open thermocouple was detected.
Solution This is usually not a I/O pack or terminal board failure if other thermocouples are working correctly.
Check the field wiring, including shields.
Check the installation of the I/O pack on the terminal board.
Replace the I/O pack.
YUAA Universal I/O Modules GEH-6855_Vol_II System Guide 219