8.4 YVIB Specific Diagnostic Alarms
The following alarms are specific to the YVIB I/O pack.
32
Description Channel [ ] A/D Converter Calibration Failure
Possible Cause The I/O pack failed to auto-calibrate when powered on.
Solution Replace the I/O pack.
33-45
Description TVBA Analog Input [ ] exceeded limits
Possible Cause
The terminal point voltage is outside of limits for the sensor type.
The Bias level (DC offset), Gain, or sensor limits are improperly set for the sensor/channel.
Open connection between sensor and terminal board
Solution
Verify that the sensor configuration is correct.
Check for the proper voltage at the terminal board point on the sensor.
Check the electrical continuity between sensor and terminal board.
Replace the I/O pack or terminal board.
46
Description Channel [ ] D/A Converter Calibration Failure
Possible Cause The board failed to auto-calibrate when powered on.
Solution Replace the I/O pack.
47
Description Initialization Error Detected
Possible Cause An I/O pack has failed.
Solution Replace the I/O pack.
YVIB Vibration Monitor Modules GEH-6855_Vol_II System Guide 271