469
Description UDH EGD fault detected by the R processor
Possible Cause
UDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered on and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the processor module.
470
Description UDH EGD fault detected by the S processor
Possible Cause
UDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered up and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the producer processor module.
471
Description UDH EGD fault detected by the T processor
Possible Cause
UDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered up and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the producer processor module.