10.8.6 Specifications
Item
JPDS Specification
Inputs
Three 9-pin connections for 28 V dc Power Supply inputs
One 50-pin ribbon cable with diagnostic data from upstream boards
One 5-screw terminal block for daisy chaining power distribution boards
25 A max each
±5 V max
35 A max per screw
Outputs
Six 6-pin connections for either JPDP or JPDL boards
Three 2-pin connections for CPCI control rack power
Three 2-pin connections, filtered and fused, for auxiliary devices
One 50-pin ribbon cable with diagnostic data to downstream boards
One 5-screw terminal block for daisy chaining power distribution boards
One 2-pin connection for 28 V dc power to the PPDA pack
One 62-pin D-shell connection for PPDA power diagnostic pack
13 A max per pin
12.5 A max per pin
1.6 A at 20 °C (derated to 0.8 A at 70 °C)
positive temperature coefficient fuse
±5 V max
35 A max per screw
0.25 A max
±5 V max
Ambient Rating for
Enclosure Design
-40 to 70ºC (-40 to 158 ºF)
Board Dimensions
16.51 cm high x 17.8 cm wide (6.5 in x 7.0 in)
Mounting
DIN-rail mounting
Base mounted steel bracket
10.8.7 Diagnostics
Diagnostic signals are obtained and routed into the PPDA I/O pack as follows:
An electronic ID identifying the board type, revision, and serial number
Three analog P28 voltage readings for R, S, and T bus
Each power supply connector (JR1, JS1, JT1) has provisions for a dry contact indicating power supply status. JPDS
conditions these signals and places them in the feedback signal set.
Auxiliary supply status feedback from downstream of the fuses provides three feedback signals to PPDA.
JPDS contains test rings for 28 V dc power from the three internal circuits, 28PR, 28PS, and 28PT. Each test ring has a series
10k resistor isolating the ring and a single grounded ring, 28N, for the return path. These can be used to measure the 28 V dc
power voltage using external test equipment.
Note Fuse and dry contacts failure diagnostics will not be generated if InputDiagEnab on the respective dc input (R/S/T) is
set to Disable or the dc input is below the low limit threshold, 5 V.
Also, dry contact diagnostics will not be generated if the user selects NoDryCnt on the input on which a dry contact exists.
394 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II