EasyManua.ls Logo

GE Mark VIeS - Firmware;Configuration Incompatibility Error; Firmware;Io Configuration Incompatibile; V Pwr Supply Voltage Is Low

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Description Firmware/Configuration Incompatibility Error;Firmware: [ ] Config: [ ]
Possible Cause I/O pack or module configuration files are incompatible with the firmware. Files have wrong revision.
Solution
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
31
Note This alarm is obsolete.
Description Firmware/IO Configuration Incompatibile;Firmware: [ ] IO Config: [ ]
Possible Cause
I/O pack or module configuration files are incompatible with the firmware.
The files have the wrong revision.
Solution
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O module and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
256
Description [ ]V Pwr supply voltage is low
Possible Cause Input voltage dropped below 18 V. I/O pack or module input power is required to be within range 28 V
±5%. I/O pack or module operation will be compromised or may stop completely.
Solution
If PPDA is available to monitor control cabinet power, check the I/O pack or module for active alarms.
Check the I/O pack or module power within the control cabinet; begin with power supplies and work toward the affected
I/O pack or module.
450 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Table of Contents

Related product manuals