266
Description Configuration file load error - invalid file length
Possible Cause
During commissioning or maintenance:
• The configuration file in the I/O pack or module does not have the correct size to match the application code that is
loaded.
During normal operation:
• Hardware failure
Solution
During commissioning or maintenance:
• Confirm the correct installation of the ToolboxST application. Rebuild the application and download the firmware and the
application code to the affected I/O pack or module.
During normal operation:
• Replace the I/O pack or module.
267
Description Firmware Load Error
Possible Cause
During commissioning or maintenance:
• Incompatible version of firmware downloaded
During normal operation:
• There is a hardware failure.
Solution
During commissioning or maintenance:
• Confirm the correct installation of the ToolboxST application.
• Ensure that each I/O pack or module is upgraded to the latest version. From the ToolboxST application, right-click each
I/O pack or module and selecting Upgrade.
• Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
During normal operation:
• Replace the I/O pack or module.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 455