264
Note This alarm is obsolete.
Description Firmware/Configuration Incompatibility Error
Possible Cause
• I/O pack or module configuration files are incompatible with the firmware.
• The files have the wrong revision.
Solution
• Confirm the correct installation of the ToolboxST application.
• Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
• Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
265
Description Configuration file load error - invalid I/O header size
Possible Cause
During commissioning or maintenance:
• Build error
• Controller EGD revision code is not supported
• Incompatible version of the I/O pack or module firmware was downloaded
During normal operation:
• There is a hardware failure.
Solution
During commissioning or maintenance:
• Confirm the correct installation of the ToolboxST application.
• Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
• Rebuild the application, and download the firmware and application code to the affected I/O module.
During normal operation:
• Replace the I/O pack or module.