348
Description Intermittent communications on IONet1 - Packet loss exceeded [ ]
Possible Cause
Power cycled on I/O producer (controller or I/O pack or module)
IONet malfunction
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet1
Solution
Check for evidence of pack restart (diagnostic alarms, error logs).
Faulty Ethernet cable from pack to network switch and/or from switch to controller. Replace cable(s).
Replace the I/O pack or module.
Faulty network switch; place the I/O pack or module's Ethernet cable into an empty port. If problem persists, replace the
network switch.
349
Description Intermittent communications on IONet2 - Packet loss exceeded [ ]
Possible Cause
Power cycled on I/O producer (controller or I/O pack or module)
IONet malfunction
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet2
Solution
Check for evidence of pack restart (diagnostic alarms, error logs).
Faulty Ethernet cable from pack to network switch and/or from switch to controller. Replace cable(s).
Replace the I/O pack or module.
Faulty network switch; place the I/O pack or module's Ethernet cable into an empty port. If problem persists, replace the
network switch.
350
Description Intermittent communications on IONet3 - Packet loss exceeded [ ]
Possible Cause
Power cycled on I/O producer (controller or I/O pack or module)
IONet malfunction
I/O message corruption
Communication errors occurred on more than 5% of data transmissions on IONet3
Solution
Check for evidence of pack restart (diagnostic alarms, error logs).
Faulty Ethernet cable from pack to network switch and/or from switch to controller. Replace cable(s).
Replace the I/O pack or module.
Faulty network switch; place the I/O pack or module's Ethernet cable into an empty port. If problem persists, replace the
network switch.