175
Description JPDC-Fuse FU73 or FU74 (J7B connector) is blown or SW7B switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
176
Description JPDC-Fuse FU75 or FU76 (J7C connector) is blown or SW7C switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
PDM Power Distribution Modules GEH-6855_Vol_II System Guide 347