62, 65
Description JPDM-[ ] P28v-R aux output fuse (JAR connector) not OK
Possible Cause
The auxiliary output JAR fuse has exceeded its current rating (3.75 A at 20°C, 83 °F) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 3.75 A.
The fuse is self-resetting. Refer to the help documentation.
63, 66
Description JPDM-[ ] P28v-S aux output fuse (JAS connector) not OK
Possible Cause
The auxiliary output JAS fuse has exceeded its current rating (3.75 A at 20°C, 83 °F) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 3.75 A.
The fuse is self-resetting. Refer to the help documentation.
64, 67
Description JPDM-[ ] P28v-T aux output fuse (JAT connector) not OK
Possible Cause
The auxiliary output JAT fuse has exceeded its current rating (3.75 A at 20°C, 83 °F) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 3.75 A.
The fuse is self-resetting. Refer to the help documentation.
326 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II