Parameter values for quantizing refer to a percentage based on the
maximum input. Therefore, if the value is set to 1% of the analog maximum
input (60Hz), the output frequency will increase or decrease by 0.6Hz per
0.1V difference.
When the analog input is increased, an increase to the input equal to 75%
of the set value will change the output frequency, and then the frequency will
increase according to the set value. Likewise, when the analog input
decreases, a decrease in the input equal to 75% of the set value will make
an initial change to the output frequency.
As a result, the output frequency will be different at acceleration and
deceleration, mitigating the effect of analog input changes over the output
frequency.
[V1 Quantizing]