Learning Basic Features
4.1.3.2 Setting a Frequency Reference for -1010V Input
Set the Frq (Frequency reference source) code in the Operation group to 2 (V1), and then
set code 06 (V1 Polarity) to 1 (bipolar) in the Input Terminal group (IN). Use the output
voltage from an external source to provide input to V1.
[V1 terminal wiring]
[Bipolar input voltage and output frequency]
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
Operation
Frq
Frequency reference
source
Freq Ref
Src
2
V1
012
-
In
01
Frequency at
maximum analog input
Freq at
100%
60.00
0 Max
Frequency
Hz
05
V1 input monitor
V1 Monitor
0.00
0.0012.00V
V
06
V1 polarity options
V1 Polarity
1
Bipolar
01
-
12
V1 minimum input
voltage
V1- volt x1
0.00
10.000.00V
V
13
V1 output at minimum
voltage (%)
V1- Perc y1
0.00
-100.000.00%
%