Table of Functions
321
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
13
31
0h140F
PM S/L speed
controller
integral gain1
ASR P
Gain 1
0~5000
150
X/A
X
P
15
31
0h1410
PM S/L speed
controller
proportional
gain2
ASR P
Gain 1
0~5000
100
X/A
X
P
16
31
0h1410
PM S/L speed
controller
integral gain2
ASR P
Gain 1
0~9999
150
X/A
x
P
20
30
0h1414
Sensorless 2
nd
gain display
setting
SL2 G
View Sel
0
No
0:No
O/A
X
I
p.190
1
Yes
21
30
0h1415
Sensorless
speed
controller
proportional
gain1
ASR-SL
P Gain1
0-5000(%)
Depen
dent
on
motor
setting
O/A
X
I
p.190
22
30
0h1416
Sensorless
speed
controller
integral gain1
ASR-SL I
Gain1
10-9999(ms)
O/A
X
I
p.190
23
32
0h1417
Sensorless
speed
controller
proportional
gain2
ASR-SL P
Gain2
1.0-1000.0(%)
O/A
X
I
p.190
24
32
0h1418
Sensorless
speed
controller
integral gain2
ASR-SL I
Gain2
1.0-1000.0(%)
O/A
X
I
p.190
25
32
0h1419
Sensorless
speed
controller
integral gain 0
ASR-SL I
Gain0
10~9999(ms)
O/A
X
I
-
26
32
0h141A
Flux estimator
proportional
gain
Flux P
Gain
10-200(%)
O/A
X
I
p.190
27
32
0h141B
Flux estimator
integral gain
Flux I Gain
10-200(%)
O/A
X
I
p.190
28
32
0h141C
Speed
S-Est P
0-32767
O/A
X
I
p.190
32
Displayed when dr.09 is set to 4 (IM Sensorless) and Cn.20 is set to 1 (YES).