Table of Functions
322
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
estimator
proportional
gain
Gain1
29
32
0h141D
Speed
estimator
integral gain1
S-Est I
Gain1
100-1000
O/A
X
I
p.190
30
32
0h141E
Speed
estimator
integral gain2
S-Est I
Gain2
100-10000
O/A
X
I
p.190
31
32
0h141F
Sensorless
current
controller
proportional
gain
ACR SL
P Gain
10-1000
O/A
X
I
p.190
32
32
0h1420
Sensorless
current
controller
integral gain
ACR SL I
Gain
10 -1000
O/A
X
I
p.190
33
33
0h1421
PM D-axis
back-EMF
estimation gain
[%]
PM EdGain
Perc
0~300.0[%]
100.0
X/A
X
P
34
33
0h1422
PM Q-axis
back-EMF
estimation gain
[%]
PM EqGain
Perc
0~300.0[%]
100.0
X/A
X
P
35
33
0h1423
Initial pole
position
detection retry
number
PD Repeat
Num
0~10
2
X/A
X
P
36
33
0h1424
Initial pole
position
detection pulse
interval
Pulse
Interval
1~100
20
X/A
X
P
37
33
0h1425
Initial pole
position
detection
current level
[%]
Pulse
Curr %
10~100
15
X/A
X
P
38
33
0h1426
Initial pole
position
detection
voltage level
Pulse
Volt %
100~4000
500
X/A
X
P
33