Installing the Inverter
42
Function
Label
Name
Description
frequency
reference input
Switch between voltage (V2) and current (I2)
modes using a control board switch (SW2).
V2 Mode:
Unipolar: 010V (12V Max.)
I2 Mode
Input current: 420mA
Maximum Input current: 24mA
Input resistance: 24
TI
Pulse input for
frequency
reference input
(pulse train)
Setup or modify frequency references using pulse
inputs from 0 to 32kHz.
Low Level: 02.5V
High Level: 3.512V
(In case of Standard I/O, Pulse input TI and Multi-
function terminal P5 share the same terminal. Set
the ln.69 P5 Define to 54(TI).).
Safety
functionality
configuration
SA
Safety input A
Used to block the output from the inverter in an
emergency.
Conditions:
Normal Operation: Both the SA and SB
terminals are connected to the SC terminal.
Output Block: One or both of the SA and SB
terminals lose connection with the SC
terminal.
SB
Safety input B
SC
Safety input
power source
DC 24V, < 25mA

Table of Contents