Output/Communication Terminal Labels and Descriptions
Used to send inverter output information to
external devices: output frequency, output
current, output voltage, or a DC voltage.
Operate switch (SW3) to select the signal output
type (voltage or current) at the AO terminal.
Output Signal Specifications:
• Output voltage: 0–10V
• Maximum output voltage/current: 12V/10mA
• Output current: 0–20mA
• Maximum output current: 24mA
• Factory default output: Frequency
Analog voltage
output terminal
Use to send inverter output information, such as
output frequency, output current, output voltage,
or DC voltage to external devices.
• Output voltage: 0–10 V
• Maximum output voltage/current: 12V/10 mA
Sends pulse signals to external devices to
provide a single output value from the inverter of
either: output frequency, output current, output
voltage, or DC voltage.
Output Signal Specifications:
• Output frequency: 0–32kHz
• Output voltage: 0–12V
• Factory default output: Frequency
(In case of Standard I/O, Pulse output TO and
Multi-function output Q1 share the same
terminal. Set the OU.33Q1 Define to 38(TO).)
When connecting to a pulse between the S100
inverters,
• Multiple I/O< -> Multiple I/O : Connect to TO
-> TI, CM -> CM
• Standard I/O <-> Standard I/O : Connect to
Q1 -> P5, EG -> CM
• Multiple I/O <-> Standard I/O : Do not
support.
Multi-functional
(open collector)
Factory default output: Run
Common ground contact for an open collector
(with external power source)
External 24V
power source
Maximum output current: 150mA