43
Installing the Inverter
Output/Communication Terminal Labels and Descriptions
Function
Label
Name
Description
Analog output
AO, AO1
Voltage/Current
Output
Used to send inverter output information to
external devices: output frequency, output
current, output voltage, or a DC voltage.
Operate switch (SW3) to select the signal output
type (voltage or current) at the AO terminal.
Output Signal Specifications:
Output voltage: 010V
Maximum output voltage/current: 12V/10mA
Output current: 020mA
Maximum output current: 24mA
Factory default output: Frequency
AO2
Analog voltage
output terminal
Use to send inverter output information, such as
output frequency, output current, output voltage,
or DC voltage to external devices.
Output voltage: 010 V
Maximum output voltage/current: 12V/10 mA
TO
Pulse Output
Sends pulse signals to external devices to
provide a single output value from the inverter of
either: output frequency, output current, output
voltage, or DC voltage.
Output Signal Specifications:
Output frequency: 032kHz
Output voltage: 012V
Factory default output: Frequency
(In case of Standard I/O, Pulse output TO and
Multi-function output Q1 share the same
terminal. Set the OU.33Q1 Define to 38(TO).)
When connecting to a pulse between the S100
inverters,
Multiple I/O< -> Multiple I/O : Connect to TO
-> TI, CM -> CM
Standard I/O <-> Standard I/O : Connect to
Q1 -> P5, EG -> CM
Multiple I/O <-> Standard I/O : Do not
support.
Digital output
Q1
Multi-functional
(open collector)
DC 26V, 100mA or less
Factory default output: Run
EG
Common
Common ground contact for an open collector
(with external power source)
24
External 24V
power source
Maximum output current: 150mA