7 APPLICATION INSTRUCTIONS
7.27 Module Access Instructions
In the following program example, when M0 turns on, the information on the module mounted at I/O number 0040H is
stored in D0 and later.
[Result of reading]
Module information of the RJ71EN71 is read.
(1) Module mounting status
(2) Start of slot
(3) CPU No. 1 control
(4) MELSEC iQ-R series module
(5) Intelligent function module
(6) 32-point module
(1) Module access enabled
(2) Fixed to 0
(3) Not during online module change
(4) Fixed to 0
(5) No fuse blown
(6) Fixed to 0
(7) Fixed to 0
(8) Inter-module synchronized
(9) Fixed to 0
(10)Module ready
(11)Normal operation (no module error)
(1) A 32-point module is connected in the latter 16 points.
(2) All 0s because information is stored in D0 and D1.
(1) All 0s because information is stored in D0 and D1.
RX10 RX10RX10
RJ71EN71
RX10CPU RX10
0000H 0010H 0020H 0030H 0040H 0060H
PW
(H) (n)(d)
M0
UNIINFRD D0 K2K4
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
D0
1 1000 01110 0000 01
(1) (2) (3) (4) (5) (6)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
D1
1 0000 00010 0001 00
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
D2
1 0000 00000 0000 00
(1) (2)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
D3
0 0000 00000 0000 00
(1)