EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 1148

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1146
9 PID OPERATION INSTRUCTION
9.2 PID Operation Instruction
Setting items (arguments)
*1 When auto tuning is not used, the same number of points are occupied as when the step response method is used.
Setting items (control data)
Setting item Description Number of
occupied
points
(s1) Set value (SV) Set the set value (SV).
Auto tuning (limit cycle method)
If the set value for auto tuning differs from that for normal PID control, set a value obtained by adding a bias
value, and then set the SV back to the original value when the auto tuning flag turns off.
1 point
(s2) Process value
(PV)
Set the input value for PID operation. 1 point
(s3) Control data
*1
Auto tuning (limit cycle method)
The device areas of 29 points starting from the device specified in (s3) are used.
29 points
Auto tuning (step response method)
The device areas of 25 points starting from the device specified in (s3) are used when all of the bits 1, 2,
and 5 of (s3)+1 (Action setting (ACT)) are not 0.
The device areas of 20 points starting from the device specified in (s3) are occupied when all of the bits 1,
2, and 5 of (s3)+1 (Action setting (ACT)) are 0.
25 points
20 points
(d) Manipulated value
(MV)
Normal PID control
The user sets the initial manipulated value before execution of the instruction. After execution, the operation
result is stored.
Auto tuning (limit cycle method)
During auto tuning, the output upper limit value (ULV) or output lower limit value (LLV) is output automatically.
Upon completion of auto tuning, the given MV is set.
Auto tuning (step response method)
The user sets the step manipulated value before execution of the instruction. During auto tuning, the MV
cannot be changed by the PID instruction.
1 point
Operand: (s3)
Device Item Description Remarks
+0 Sampling time (T
S
) 1 to 32767 [ms] The sampling time must be longer than the operation
cycle of the programmable controller.
+1 Action setting (ACT) Bit 0 0: Direct action
1: Reverse action
Action direction specification
Bit 1 0: Input variation alarm disabled
1: Input variation alarm enabled
Bit 2 0: Output variation alarm disabled
1: Output variation alarm enabled
Do not turn on bit 2 and bit 5 at the same time.
Bit 3 Reserved
Bit 4 0: Auto tuning disabled
1: Auto tuning enabled
Bit 5 0: No output upper/lower limit value setting
1: Output upper/lower limit value setting
enabled
Do not turn on bit 2 and bit 5 at the same time.
Bit 6 0: Step response method
1: Limit cycle method
Auto tuning mode selection
Bits 7 to 15 Reserved
+2 Input filter constant () 0 to 99 [%] 0 = No input filter
+3 Proportional gain (K
P
) 1 to 32767 [%]
+4 Integral time (T
I
) 1 to 32767 [ 100ms] 0 = (No integration)
+5 Derivative gain (K
D
) 0 to 200 [%] 0 = No derivative gain
+6 Derivative time (T
D
) 1 to 32767 [ 10ms] 0 = No derivation
+7 to +19 These areas are used for internal processing of PID operation, and therefore data cannot be changed.
+20
*1
Input variation (increase) alarm setting
value
0 to 32767 Enabled when the bit 1 of (s3)+1 (Action direction
(ACT)) is 1.
+21
*1
Input variation (decrease) alarm setting
value
0 to 32767 Enabled when the bit 1 of (s3)+1 (Action direction
(ACT)) is 1.
+22
*1
Output variation (increase) alarm setting
value
0 to 32767 Enabled when the bit 2 of (s3)+1 (Action direction
(ACT)) is 1, and the bit 5 is 0.
Output upper limit setting value -32768 to 32767 Enabled when the bit 2 of (s3)+1 (Action direction
(ACT)) is 0, and the bit 5 is 1.

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals