1296
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■Input data
■Block memory
■Operation constant
Operand: (s1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value -999999 to 999999 Single-precision
real number
User
+2 e1 Operation
control signal
0: Dead time
1: No dead time
16-bit unsigned
binary
User
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
+2 BB BB1 Data sufficiency
bit
0: Data sufficient
1: Data insufficient
16-bit unsigned
binary
System
Operand: (s2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
ST Data sampling
interval
0 to 999999
Set a value within the following range.
Single-precision
real number
1.0 User
+2 SN Sampling count 0 to 48 16-bit unsigned
binary
0User
+3
+4
Ys Output initial
value
-999999 to 999999 Single-precision
real number
0.0 User
+5 OCHG Initial output
switching
0: Output E1 when e1 has changed from 1 to 0 SN times.
1: Output Ys up to SN.
16-bit unsigned
binary
0User
b15 b0
BB1
...
©T
ST
<=32767