EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 1298

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1296
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
Input data
Block memory
Operation constant
Operand: (s1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value -999999 to 999999 Single-precision
real number
User
+2 e1 Operation
control signal
0: Dead time
1: No dead time
16-bit unsigned
binary
User
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
+2 BB BB1 Data sufficiency
bit
0: Data sufficient
1: Data insufficient
16-bit unsigned
binary
System
Operand: (s2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
ST Data sampling
interval
0 to 999999
Set a value within the following range.
Single-precision
real number
1.0 User
+2 SN Sampling count 0 to 48 16-bit unsigned
binary
0User
+3
+4
Ys Output initial
value
-999999 to 999999 Single-precision
real number
0.0 User
+5 OCHG Initial output
switching
0: Output E1 when e1 has changed from 1 to 0 SN times.
1: Output Ys up to SN.
16-bit unsigned
binary
0User
b15 b0
...
e1
b15 b0
BB1
...
©T
ST
<=32767
b15 b0
...
OCHG

Table of Contents