11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1339
11
■Input data 1
■Block memory
■Operation constant
Operand: (s1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value 1 -999999 to 999999 [%] Single-precision
real number
User
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
+2 BB BB1 Alarm
0: No alarm
1: Alarm
16-bit unsigned
binary
System
BB2 Output upper
limit alarm
BB3 Output lower
limit alarm
BB4 Output variation
rate alarm
Operand: (s2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
NMAX Output
conversion
upper limit
-999999 to 999999 Single-precision
real number
100.0 User
+2
+3
NMIN Output
conversion
lower limit
-999999 to 999999 Single-precision
real number
0.0 User
+4 TRK Tracking bit 0: Tracking not performed
1: Tracking performed
16-bit unsigned
binary
0User
+5 SVPTN Set value
pattern
(1) Input value selection (e1)
Specify whether to use E1 or E2 for the input value.
0: E1
1: E2
(2) Use of input value 1 (E1)
Specify whether to use the input value 1 (E1) or not.
0: Use
1: Not use
(3) Use of input value 2 (E2)
Specify whether to use the input value 2 (E2) or not.
0: Use
1: Not use
(4) Input value 1 (E1) pattern
Specify whether to use the upper loop MV as the input value 1
(E1) or not.
0: E1 is the upper loop MV.
1: E1 is not the upper loop MV.
(5) Input value 2 (E2) pattern
Specify whether to use the upper loop MV as the input value 2
(E2) or not.
0: E2 is the upper loop MV.
1: E2 is not the upper loop MV.
16-bit unsigned
binary
1EH User
b15 b0b1b2b3
BB1
BB2
BB3
BB4
...
b15 b0b1b2b3b4
(1)(2)(3)(4)(5)
...