1340
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+1 MODE Control mode 0 to FFFFH 16-bit unsigned
binary
8H User/
system
+3 ALM Alarm detection 0 to FFFFH
SPA
0: Loop RUN
1: Loop STOP
DMLA, MHA, MLA
0: No alarm
1: Alarm
16-bit unsigned
binary
4000H User/
system
+4 INH Disable alarm
detection
0 to FFFFH
0: Alarm detection enabled
1: Alarm detection disabled
16-bit unsigned
binary
4000H User/
system
+10
+11
PV Selecting a
Value
RL to RH Single-precision
real number
0.0 System
+12
+13
MV Manipulated
value
-10 to 110 [%] Single-precision
real number
0.0 User/
system
+14
+15
PV1 Process value 1 RL to RH Single-precision
real number
0.0 System
+16
+17
PV2 Process value 2 RL to RH Single-precision
real number
0.0 System
+18
+19
MH Output upper
limit value
-10 to 110 [%] Single-precision
real number
100.0 User
+20
+21
ML Output lower
limit value
-10 to 110 [%] Single-precision
real number
0.0 User
+22
+23
RH Engineering
value upper limit
-999999 to 999999 Single-precision
real number
100.0 User
+24
+25
RL Engineering
value lower limit
-999999 to 999999 Single-precision
real number
0.0 User
+26 SLNO Selected No.
(1) Selection of input value 1 (E1)
0: Not selected
1: Selected
(2) Selection of input value 2 (E2)
0: Not selected
1: Selected
16-bit unsigned
binary
0 System
+48
+49
DML Output variation
rate limit value
0 to 100 [%] Single-precision
real number
100.0 User
b15 b9b10 b1b2b3b4b5b6b7b8 b0
CMV
CSV
LCM
LCA
LCC
MAN
AUT
CAS
CMB
CAB
CCB
...
b15 b14 b11
... ...
b1 b0
DMLA
SPA
MHA
MLA
b15
b11
b0b1
......
ERRI
DMLI
MLI
MHI