1348
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■Input data
■Block memory
■Operation constant
■Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
Operand: (s1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Output addition
value
-999999 to 999999 Single-precision
real number
User
+2
+3
E2 Output
subtraction
value
-999999 to 999999 Single-precision
real number
User
+4
+5
E3 Output set value -999999 to 999999 Single-precision
real number
User
+6 e1 Operation
output signal
e1
0: Manual mode
1: Automatic mode
e2
0: Do not add
1: Add
e3
0: Do not subtract
1: Subtract
16-bit unsigned
binary
User
e2 Output addition
signal
e3 Output
subtraction
signal
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
Operand: (s2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
d1 Output upper
limit value
0 to 999999 Single-precision
real number
1.0 User
+2
+3
d2 Output lower
limit value
-999999 to 999999 Single-precision
real number
1.0 User