Loading...
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1349
11
Processing details
This instruction increases or decreases the output value (BW) at a fixed rate.
The instruction performs the following processing as specified by operation output signal (e1), output addition signal (e2), and
output subtraction signal (e3).
In manual mode (operation output signal (e1) = 0), the output value (BW) equals the output set value (E3).
In automatic mode (operation output signal (e1) = 1), the instruction performs the following operations as specified by the
output addition signal (e2) and output subtraction signal (e3).
Operation error
e2 e3 BW
10BW=BW+|E1|T
provided that when d1BW, BW equals d1.
01BW=BW-|E2|T
provided that when BWd2, BW equals d2.
11BW=BW
00
Error code Error content
3402H The value specified by (s1) or (s2) is a subnormal number or NaN (not a number).
3403H An overflow has occurred.
1s
E2
E1
1s
e3=1e2=1
100
t
d1
E3
d2
e1