15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1471
15
Control data
Operand: (s1)
Device Item Description Setting range Set by
+0 Execution/error
completion type
(1) Execution type (b0)
0: No arrival acknowledgment
When the target station is in the own network: Completed when data has been sent
from the own station.
When the target station is in another network: Completed when data has arrived the
relay station of the own network.
1: Arrival acknowledgment used
Sending data is completed when the data is written to the target station.
(2) Error completion type (bit 7)
Specify whether to set clock data when completed with an error.
0: Do not set data in (s1)+11 and later at completion with an error.
1: Set data in (s1)+11 and later at completion with an error.
(3) Arrival check time setting (bit 8)
0: 1s units
1: 100ms units
(4) Target station address specification method (b15)
0: Specify "network No." in (s1)+4, and "station number" in (s1)+5.
1: Specify the IP address in (s1)+4, 5 (Ethernet only)
0000H
0001H
0080H
0081H
0100H
0101H
0180H
0181H
8000H
8001H
8080H
8081H
8100H
8101H
8180H
8181H
User
+1 Completion status The completion status is stored upon completion of the instruction.
•0: Normal
Other than 0: Error (error code)
System
+2 Own station channel Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
1 to 18 User
+3 Target station CPU type Specify the CPU type of the target station.
0000H: Addressed to target station CPU (control CPU)
03D0H: Addressed to control system CPU
03D1H: Addressed to standby system CPU
03D2H: Addressed to system A CPU
03D3H: Addressed to system B CPU
03E0H: Addressed to multiple CPU No. 1
03E1H: Addressed to multiple CPU No. 2
03E2H: Addressed to multiple CPU No. 3
03E3H: Addressed to multiple CPU No. 4
03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
User
b15
00(4)
(3) (2) (1)
b7b8 b0
……
Completed
Target
station
Request
source
Completed
Target
station
Request
source
Relay
station
Completed
Target
station
Request
source
Relay
station
Target
station
Completed