15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
■Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■Control data
■Receive data
The continuous area (a maximum of 960 words) for the receive data length ((s)+9) is required in the receive
data storage device (d1).
Operand Bit Word Double word Indirect
specification
Constant Others
(U)
X, Y, M, L,
SM, F, B,
SB, FX, FY
J\ T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(U) G.RECVS
Z.RECVS
(s)
*2
(d1)
*2
(d2)
*1
*3
Operand: (s)
Device Item Description Setting range Set by
+0 System area
+1 Completion status The completion status is stored upon completion of the instruction.
•0: Normal
• Other than 0: Error (error code)
System
+2 Own station storage
channel
Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
1 to 8, 11 to 18 User
+3 Channel used by send
station
The channel number (1 to 8) used by the sending station is stored. 1 to 8 System
+4 Send station network
number
The network number (1 to 239) of the sending station is stored. 1 to 239 System
+5 Sending-station No. The station number of the sending station is stored.
[Ethernet or CC-Link IE Controller Network]
• 1 to 120: Station number (receiving from station number)
[CC-Link IE Field Network]
• 125: Master station
• 1 to 120: Local station, intelligent device station, submaster station
1 to 120, 125 System
+6 to +8 System area
+9 Receive data length The number of data received and stored in (d1)+0 to (d1)+ is stored.
• 0: No receive data
• 1 to 960: Number of words of received data
0 to 960 System
Operand: (d1)
Device Item Description Setting range Set by
+0 to + Receive data Receive data is stored. System