18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.6 Reading the Module Status Information of an Intelligent Device Station
1625
18
■Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■Control data
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $ J U
(J/U) J(P).S
INFST
RD
G(P).
SINFS
TRD
(s)
*2
(d1)
*2
(d2)
*1
*3
Operand: (s)
Device Item Description Setting range Set by
+0 Error completion type
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data at completion with an error in (s)+12 and later.
• 1: Set data at completion with an error in (s)+12 and later.
(2) Arrival check time setting (bit 8)
• 0: 1s units
• 1: 100ms units
0000H
0080H
0100H
0180H
User
+1 Completion status The instruction completion status is stored.
•0: Normal
• Other than 0: Error (error code)
System
+2 Own station channel
*1
Specify the channel to be used by own station. 1 to 32 User
+3 to +4 Not used System
+5 Target station number Specify the station number of the target station. 1 to 120 User
+6 Not used System
+7 Number of resends ■Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s)+8.
• 0 to 15 (times)
■At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
0 to 15 User/
system
+8 Arrival monitoring time Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s)+7.
■When "0" is specified in bit 8 of (s)+0
•0: 10s
• 1 to 32767: 1 to 32767s
■When "1" is specified in bit 8 of (s)+0
•0: 10s
• 1 to 65535: 1 to 65535 100ms
0 to 65535 User
+9 to +10 Not used System
+11 Clock setting flag The validity status (valid or invalid) of the data in (s)+12 and later is stored. Note that
the data in (s)+12 and later is not cleared even when the instruction is completed
successfully.
• 0: Invalid
• 1: Valid
System
b15
00
(2) (1)
b7b8 b0
……