18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.7 Setting Parameters
1631
18
*1 If a value outside the setting range is set, the instruction will complete with an error.
*2 If "Invalid" is set, the default parameter will be used.
*3 Set value 121 is available only if the submaster function is used.
For the startup in the local station, only Data link faulty station setting (bit 8 of (s1)+1) and CPU STOP time
output setting (bit 9 of (s1)+1) will be valid. Any other changed settings will be ignored during execution of the
instruction, without causing an error.
Network configuration setting data (for master station setting only)
+3 Constant link scan time Sets the constant link scan time.
0: No operator
1 to 200: Constant link scan time
0 to 200 User
+4
+5
IP address Sets the IPv4 network address (i.e. IP address) when the IP packet transfer function
is used.
(s1)+4: Dummy
(s1)+5: Network address
00000001H to
FFFFFFFFH
User
Operand: (s2)
Device Item Description Setting
range
*1
Set by
+0 For 1st
module
Slave station
setting
information
Sets the station type, the number of occupied stations, and the station number.
(1) Station number
1 to 120: Station number
0: Master station
(2) Number of occupied stations
•1: Fixed
(3) Station type
0: Remote I/O station
1: Remote device station
2: Intelligent device station
3: Local station (master-slave system)
4: Submaster station
F: Master station
Left User
+1 RX/RY offset Sets the offset value from the head of RX/RY (in units of 16 points).
*2
0 to 16368 User
+2 Number of RX/
RY points
Sets the number of RX/RY, LB points.
*2
If the station type is master or local: 0 to 2048 points
If the station type is intelligent device: 0 to 2048 points (in units of 16 points)
If the station type is remote I/O: 0 to 64 points (in units of 16 points)
If the station type is remote device: 0 to 128 points (in units of 16 points)
0 to 2048
0 to 64
0 to 128
User
+3 RWr/RWw
offset
Sets the offset value from the start of RWr/RWw (in units of 4 points).
*2
0 to 8188 User
+4 Number of RWr/
RWw points
Sets the number of RWr/RWw, LW points.
*2
If the station type is master or local: 0 to 256 points (in units of 16 points)
If the station type is intelligent device: 0 to 1024 points (in units of 4 points)
If the station type is remote device: 0 to 64 points (in units of 4 points)
0 to 256
0 to 1024
0 to 64
User
+5 to +594 User
Operand: (s1)
Device Item Description Setting range
*1
Set by
(s1)+5 (s1)+4
b15 b12 b11 b8 b7 b0
(1)(3)
……
(2)